NHT Italia
s.r.l.
Via dei Tigli, 12/14
50010 Capalle Campi Bisenzio (FI)
Tel. +39 (0) 55 8969101
Fax +39 (0) 55 8969179
Conductive
level regulators
The
conductive level regulators by NHT are suitable for controlling the
minimum and the maximum level, both input and output, of wells, tanks
and cisterns. When connected to the appropriate probe detectors and
inserted in the control circuits of the pump, they are able to mantain
the level of the liquids within the predetermined limits. Both the
the devices come equipped with insulated probes which must be placed
in the liquid to be controlled. At first, with the probes free, the
output relay is at rest; when the maximum level probe is reached by
the liquid, the relay is automatically activated. When the level descends
below the minimum level probe the relay is deactivated.
This
series can be characterized by monotension or multitension output
and is composed of three basic models.
LC 103 / LC 104 with normal sensitivity. Models appropriated
for the control of water and in general of liquids whose conductivity
is max 5 Kohm.
LC 103 / LC 104 with high sensitivity. These are the regulators
most appropriate for the control of liquids with a low conductivity
such as rain water. These models permit the control of liquids with
a total conductivity up to 70 Kohm.
LC 103 / LC 104 with variable sensitivity. These models are
indispensable for the control of liquids whose conductivity is unknown.
They are suitable for liquids with a conductivity of up to a maximum
of 100 Kohm.
Supply
voltage
MonotensionMonoSocket
24-117-230
Vca
MultitensionBiSocket
24/48
- 117/230 Vca
Sensitivity
Normal
up
to 5 Kohm
High
up
to 70 Kohm
Variable
from
0 to 100 Kohm
Relay
consumption
ACI
resistive
5A
250 Vca
AC
inductive
2A
250 Vca
DC
inductive
5A
30 Vca
Electrode
voltage
10
Vca
Power
consumption
2
VA
Dielectric
strenght
2000
Vca
Renspose
time
100
ms
Operating
temperature
-10°
÷ +50° C
Storage
temperature
-10°
÷ +80° C
Dimensions
79x36x88
mm
Weight
200
gr
Housing
Noryl
(PPO) UL 94 VO
Connection
Level Control 103
octal
socket
Connection
Level Control 104
undecal
socket
Mounting
DIN
EN 50022
Accessories
included
3
probes
Note:
Max lenght probe cable 70 ÷ 80 mt with high or variable
sensitivity, 1000 mt with normal sensitivity.